Area | Microservice | Gaps Identified | Criticality | Why Important | Recommended Actions |
---|
Device | OPC UA | Missing | | New installations of SCADA systems are typically expected to be compliant with the OPC UA standard |
|
Device | OPC DA | Missing | | Although OPC UA is an emerging standard, E&P Companies are still massively using OPC DA in legacy systems and in some cases in new installations as well |
|
Device | Modbus | Seems like the current Modbus implementation is querying 1 register at a time on the Modbus Slave. Modbus requests should be grouped together requisting multiple registers with a single call. | | Sending too many requests is invasive on the PLC which needs to conserve CPU cycles to perform its control duties |
|
Device | Zigbee | Missing | | Wireless sensors are slowly gaining traction for non-critical measurements as wiring can be tough in certain constrained environments. Zigbee would be a good option. |
|
Device | LoRa | Missing | | Wireless sensors are slowly gaining traction for non-critical measurements as wiring can be tough in certain constrained environments. LoRa would be a good option. |
|
Device | GPS | Missing | | Could a GPS DS serve to get the coordinates (lat/long - 2 floating point metrics) from the gateway? |
|
Device | Profinet | Missing | | Siemens hardware is used in many Oil&Gas installations (e.g. North Sea) and Profinet I/O would be a suitable protocol for interfacing with EdgeX |
|
Device | DDS | Missing | | DDS is used in drilling for data messaging on critical items |
|
Core | Data |
|
|
|
|
Core | Metadata |
|
|
|
|
Core | Command |
|
|
|
|
Support | Rules Engine / Analytics |
|
|
|
|
Support | Scheduling |
|
|
|
|
Support | Alerts & Notifications |
|
|
|
|
Support | Logging | Need to be able to specify persistency policies for type of logs | | Different logs are required for liability purposes and can be assessed in case of incidents |
|
Export | Client Registration & Distribution | Missing mechanism for backfilling historical data. (perform an export job from start-timestamp to end-timestamp). | | Retrieve historical data back to the cloud |
|
System | System Management | Connection loss handling: changes made while offline will be cached and sent when connection is re-established | | Edges could be often disconnected |
|
Security | Security | Need to lock down access to EdgeX from remote hosts not authenticated | | High security concerns |
|
Code
If specific code addressing some of the identified gaps will be implemented as part of this project, the contributor will submit a PR on the relevant github repository.
...